Quadruplex Service Drop Cable
-
Refined Matterial
-
Standard Process
-
Free Sample & Test
-
Long Life-circle
Product Details
Applications
Used to supply 3-phase power, usually from a pole-mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for cross-linked polyethylene (XLPE) insulated conductors.
Specification
Quadruplex service drop cable meets or exceeds the following ASTM specifications:
• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
• B-231 Aluminum Conductors, Concentric-Lay-Stranded.
• B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
• B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
• ICEA S-76-474-Neutral-supported Power Cable Assemblies With Weather-Resistant Extruded Insulation Rated 600Volts
Standard Specification
Quadruplex - AAC
Code Word |
Phase Conductor | Bare Neutral Messenger | Weight Per 1000ft.(Ibs.) |
Allowable Ampacities+ |
||||||
Size (AWG) |
Stranding | Insul. Thick. (mils) |
Size (kcmil) |
Stranding | Rated Strength (Ibs.) |
XLP | POLY | XLP | POLY | |
AAC NEUTRAL-MESSENGER | ||||||||||
Clydesdale | 4 | 1 | 45 | 4 | 7 | 881 | 198 | 198 | 100 | 80 |
Pinto | 4 | 7 | 45 | 4 | 7 | 881 | 211 | 211 | 100 | 80 |
Mustang | 2 | 7 | 45 | 2 | 7 | 1350 | 318 | 318 | 135 | 105 |
Criollo | 1/0 | 9 | 60 | 1/0 | 7 | 1990 | 503 | 503 | 180 | 140 |
Percheron | 2/0 | 11 | 60 | 2/0 | 7 | 2510 | 619 | 619 | 205 | 160 |
Hanovarian | 3/0 | 17 | 60 | 3/0 | 19 | 3310 | 764 | 764 | 235 | 185 |
Oldenburg | 4/0 | 18 | 60 | 4/0 | 19 | 4020 | 945 | 945 | 275 | 210 |
Lippizaner | 336.4 | 19 | 80 | 336.4 | 19 | 6146 | 1519 | 1519 | 370 | 280 |
+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2ft./sec. wind in sun. |
Quadruplex - AAAC
Code Word |
Phase Conductor | Bare Neutral Messenger | Weight Per 1000ft.(Ibs.) |
Allowable Ampacities+ |
|||||||
Size (AWG) |
Stranding | Insul. Thick. (mils) |
Equiv. Dia. (AWG)++ |
Size (kcmil) |
Stranding | Rated Strength (Ibs.) |
XLP | POLY | XLP | POLY | |
6201 ALLOY NEUTRAL-MESSENGER | |||||||||||
Bay | 6 | 1 | 45 | 6 | 30.58 | 7 | 1110 | 137 | 137 | 75 | 60 |
French Coach | 6 | 7 | 45 | 6 | 30.58 | 7 | 1110 | 146 | 146 | 75 | 60 |
German Coach | 4 | 1 | 45 | 4 | 48.69 | 7 | 1760 | 205 | 205 | 100 | 80 |
Arabian | 4 | 7 | 45 | 4 | 48.69 | 7 | 1760 | 217 | 217 | 100 | 80 |
Belgian | 2 | 7 | 45 | 2 | 77.47 | 7 | 2800 | 328 | 328 | 135 | 105 |
Shetland | 1/0 | 9 | 60 | 1/0 | 123.3 | 7 | 4460 | 519 | 519 | 180 | 140 |
Thoroughbred | 2/0 | 11 | 60 | 2/0 | 155.4 | 7 | 5390 | 639 | 639 | 205 | 160 |
Trotter | 3/0 | 17 | 60 | 3/0 | 195.7 | 7 | 6790 | 789 | 789 | 235 | 185 |
Walking | 4/0 | 18 | 60 | 4/0 | 246.9 | 7 | 8560 | 977 | 977 | 275 | 210 |
+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2ft./sec. wind in sun. ++Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201. |
Quadruplex - ACSR
Code Word |
Phase Conductor | Bare Neutral Messenger | Weight Per 1000ft.(Ibs.) |
Allowable Ampacities+ |
||||||
Size (AWG) |
Stranding | Insul. Thick. (mils) |
Size (kcmil) |
Stranding | Rated Strength (Ibs.) |
XLP | POLY | XLP | POLY | |
ACSR NEUTRAL-MESSENGER | ||||||||||
Morochuca | 6 | 1 | 45 | 6 | 43252 | 1190 | 145 | 145 | 75 | 60 |
Chola | 6 | 7 | 45 | 6 | 43252 | 1190 | 153 | 153 | 75 | 60 |
Morgan | 4 | 1 | 45 | 4 | 43252 | 1860 | 217 | 217 | 100 | 80 |
Hackney | 4 | 7 | 45 | 4 | 43252 | 1860 | 229 | 229 | 100 | 80 |
Palomino | 2 | 7 | 45 | 2 | 43252 | 2850 | 347 | 347 | 135 | 105 |
Costena | 1/0 | 9 | 60 | 1/0 | 43252 | 4380 | 549 | 549 | 180 | 140 |
Grullo | 2/0 | 11 | 60 | 2/0 | 43252 | 5310 | 677 | 677 | 205 | 160 |
Suffolk | 3/0 | 17 | 60 | 3/0 | 43252 | 6620 | 837 | 837 | 235 | 185 |
Appaloosa | 4/0 | 18 | 60 | 4/0 | 43252 | 8350 | 1038 | 1038 | 275 | 210 |
Gelding | 336.4 | 19 | 80 | 4/0 | 43252 | 8350 | 1494 | 1494 | 370 | 280 |
Bronco | 336.4 | 19 | 80 | 336.4 | 43118 | 8680 | 1568 | 1568 | 370 | 280 |
+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2ft./sec. wind in sun. |