• Triplex Service Drop Cable
  • Triplex Service Drop Cable

Triplex Service Drop Cable

Conductor
Insulation
Rated Voltage
Product Highlight
  • Refined Matterial
  • Standard Process
  • Free Sample & Test
  • Long Life-circle

Product Details

Applications

Used to supply power, usually from a pole-mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for cross-linked polyethylene (XLPE) insulated conductors.

Specification

Triplex service drop cable meets or exceeds the following ASTM specifications:
• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
• B-231 Aluminum Conductors, Concentric-Lay-Stranded.
• B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
• B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
• ICEA S-76-474-Neutral-supported Power Cable Assemblies With Weather-Resistant Extruded Insulation Rated 600Volts

Standard Specification

Triplex AAC

Code
Word
Phase Conductor Bare Neutral Messenger Weight
Per 1000ft.(Ibs.)
Allowable
Ampacities+
Size
(AWG)
Stranding Insul.
Thick.
(mils)
Size
(kcmil)
Stranding Rated Strength
(Ibs.)
XLP POLY XLP POLY
AAC NEUTRAL-MESSENGER
Patella 6 7 45 6 7 563 103 103 85 70
Oyster 4 7 45 4 7 881 154 154 115 90
Clam 2 7 45 2 7 1350 233 233 150 120
Murex 1/0 7 60 1/0 7 1990 374 374 205 160
Purpura 1/0 9 60 1/0 7 1990 368 368 205 160
Nassa 2/0 7 60 2/0 7 2510 462 462 235 185
Melita 3/0 17 60 3/0 19 3310 562 562 275 215
Portunus 4/0 18 60 4/0 19 4020 696 696 315 245
Nannynose 336.4 19 80 336.4 19 6146 1118 1118 420 325
+ Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2ft./sec. wind in sun.

Triplex - AAAC

Code
Word
Phase Conductor Bare Neutral Messenger Weight
Per 1000ft.(Ibs.)
Allowable
Ampacities+
Size
(AWG)
Stranding Insul.
Thick.
(mils)
Equiv. Dia.
(AWG)++
Size
(kcmil)
Stranding Rated Strength
(Ibs.)
XLP POLY XLP POLY
6201 ALLOY NEUTRAL-MESSENGER
Minex 6 1 45 6 30.58 7 1110 101 101 85 70
Hippa 6 7 45 6 30.58 7 1110 107 107 85 70
Prawn 4 1 45 4 48.69 7 1760 152 152 115 90
Barnacle 4 7 45 4 48.69 7 1760 160 160 115 90
Shrimp 2 7 45 2 77.47 7 2800 243 243 150 120
Gammarus 1/0 7 60 1/0 123.3 7 4460 390 390 205 160
Leda 1/0 9 60 1/0 123.3 7 4460 384 384 205 160
Dungenese 2/0 7 60 2/0 155.4 7 5390 483 483 235 185
Cyclops 2/0 11 60 2/0 155.4 7 5390 474 474 235 185
Flustra 3/0 17 60 3/0 195.7 7 6790 587 587 275 215
Lepas 4/0 18 60 4/0 246.9 7 8560 728 728 315 245
+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2ft./sec. wind in sun.
++Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201.

Triplex - AAAC Reduced

Triplex - AAAC Reduced

Code
Word
Phase Conductor Bare Neutral Messenger Weight
Per 1000ft.(Ibs.)
Allowable
Ampacities+
Size
(AWG)
Stranding Insul.
Thick.
(mils)
Equiv. Dia.
(AWG)++
Size
(kcmil)
Stranding Rated Strength
(Ibs.)
XLP POLY XLP POLY
6201 ALLOY REDUCED NEUTRAL-MESSENGER
Artemia 4 1 45 6 30.58 7 1110 135 135 115 90
Crab 4 7 45 6 30.58 7 1110 143 143 115 90
Solaster 2 7 45 4 48.69 7 1760 216 216 150 120
Sandcrab 1/0 7 60 2 77.47 7 2800 347 347 205 160
Echinus 1/0 9 60 2 77.47 7 2800 341 341 205 160
Fulgar 3/0 17 60 1/0 123.3 7 4460 519 519 275 215
Arca 4/0 18 60 2/0 155.4 7 5390 643 643 315 245
+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2ft./sec. wind in sun.
++Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201.

Triplex - ACSR Reduced

Code
Word
Phase Conductor Bare Neutral Messenger Weight
Per 1000ft.(Ibs.)
Allowable
Ampacities+
Size
(AWG)
Stranding Insul.
Thick.
(mils)
Size
(kcmil)
Stranding Rated Strength
(Ibs.)
XLP POLY XLP POLY
ACSR REDUCED NEUTRAL-MESSENGER
Scallop 4 1 45 6 43252 1190 -- 142 115 90
Strombus 4 7 45 6 43252 1190 151 151 115 90
Cockle 2 7 45 4 43252 1860 228 228 150 120
Janthina 1/0 7 60 2 43252 2853 366 366 205 160
Ranella 1/0 9 60 2 43252 2853 360 360 205 160
Cavolinia 2/0 7 60 1 43252 3550 453 453 235 185
Clio 2/0 11 60 1 43252 3550 444 444 235 185
Aega 3/0 17 60 1/0 43252 4380 549 549 275 215
Cerapus 4/0 18 60 2/0 43252 5310 681 681 315 245
+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2ft./sec. wind in sun.

Triplex - ACSR

Code
Word
Phase Conductor Bare Neutral Messenger Weight
Per 1000ft.(Ibs.)
Allowable
Ampacities+
Size
(AWG)
Stranding Insul.
Thick.
(mils)
Size
(kcmil)
Stranding Rated Strength
(Ibs.)
XLP POLY XLP POLY
ACSR NEUTRAL-MESSENGER
Paludina 6 1 45 6 43252 1190 109 109 85 70
Voluta 6 7 45 6 43252 1190 114 114 85 70
Whelk 4 1 45 4 43252 1860 -- 164 115 90
Periwinkle 4 7 45 4 43252 1860 172 172 115 90
Conch 2 7 45 2 43252 2850 262 262 150 120
Neritina 1/0 7 60 1/0 43252 4380 420 420 205 160
Cenia 1/0 9 60 1/0 43252 4380 414 414 205 160
Runcina 2/0 7 60 2/0 43252 5310 520 520 235 185
Triton 2/0 11 60 2/0 43252 5310 512 512 235 185
Mursia 3/0 17 60 3/0 43252 6620 635 635 275 215
Zuzara 4/0 18 60 4/0 43252 8350 789 789 315 245
Limpet 336.4 19 80 336.4 43118 8680 1167 1167 420 325
+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2ft./sec. wind in sun.

Request for Quotation

Humble note : fields marked with * are essential for us to provide you in time and seamless services. For instant consulting, please use us live chat help, engineer is standby and ready for help.
Contact only with your permission.
Image CAPTCHA
Enter the characters shown in the image.
This question is for testing whether or not you are a human visitor and to prevent automated spam submissions.
Copyright © 2025 UME CABLE CO., LTD - All Rights Reserved